9171 Installation Guide
Proprietary & Confidential
Canoga Perkins Metro Ethernet Routing Switch
14
of
26
When there is no grounding bar in the installation environment of Ethernet switches and grounding electrodes
are not permitted to bu
ry according to the conditions, if Ethernet switches are supplied with AC power, they
can be grounded through PE cables of AC power. At this point, PE cables of AC power should be confirmed
well grounded in the power distribution room or on AC supply trans
former side.
Fig. 2
-
7: Grounding Installation Sketch Using AC PE Cable
Description:
(1)
Power input of switch
(2)
Ground terminal of switch
(3)
Power transformer
(4)
PE
(5)
3
-
core ca
ble used in AC power connection
(6)
Switch
2.3.3
Post
-
Insta
llation Checking
Check if selected power agrees with the identified power of switch:
Check if the ground wire is connected.
Check if the connections between configured cables and power input cables are correct.
Check the interface cables are arranged indoo
rs instead of outdoors, if some cables are arranged
outdoors, check if they are connected with a
n
AC power lightning protection strip and network port
lightning protector.